Compare battery capacity with inverter demand

A battery size and an inverter rating answer different questions. LoadDay shows both the energy needed across the planning horizon and the power peaks entered for the load list.

Translate nominal battery energy

The default 1,000 Wh battery is reduced by the 85% usable fraction and 90% inverter efficiency. That produces about 765 Wh delivered for this estimate, below the 1,230 Wh daily load.

delivered Wh = battery Wh x usable fraction x inverter efficiency

Review planning horizon coverage

Required battery energy divides daily Wh multiplied by planning days by usable fraction and efficiency. The default one-day plan needs about 1,607.84 nominal Wh, so the 1,000 Wh input covers about 62.2% of the selected horizon.

required battery Wh = daily Wh x planning days / (usable fraction x efficiency)

Check continuous and peak ratings

The default running load is 125 W and the entered peak sum is 220 W. Compare those values with the 1,200 W continuous and 2,400 W surge inputs, then follow the actual equipment documentation for connection and installation decisions.

Check your own scenario

Replace the illustrative inputs with measured values and dated specifications.

Open LoadDay Power Planner

Method and references

Read the full calculation method and its limits

Method and examples reviewed 2026-09-30. Examples are illustrative; input values and specifications are not independently verified.